. . Errors

5.1
Resolving simple problems
P
P
ROBLEM
The unit does not
The unit has not been switched on
work.
The unit has no power supply.
The unit does not
The unit is running in test mode.
respond to changes in
the b-touch control
panel.
The unit only moves
The unit is running in defrost mode.
air from the inside to
the outside.
The unit functions dif-
The unit is operating in a special mode.
ferently from expecta-
tions.
The unit is not circu-
One of the inlet sections and/or the con-
lating enough air.
nected ventilation units is blocked.
Manual version 4.1 (26-07-2018)
d
w
See also:
1.5
If you suspect an error, first try to resolve the problem using
the table below. You do not need to be an expert for this.
If this fails to resolve the problem, there may be a fault; in that
case, alert the installer.
ROBABLE CAUSE
Danger:
All work on the inside of the unit may only be
carried out by personnel who are technically
qualified to do so.
Warning:
Before you begin: read the safety instructions.
"Safety instructions" on page 11
W
HAT TO DO
Turn the unit on
Check the mains supply:
• isolation switch;
• unit has power.
Stop the test mode: in
menu > Maintenance > Reset system
stop
.
When the pressure different across the
plate heat exchanger is once again correct,
defrost mode will remain active for
another ten minutes. The unit will then
run in the last activated mode.
• Check which mode the unit is operat-
ing in. (Register address 221 or b-
touch menu ...)
Remove obstacles to the inlet and dis-
charge section.
en
click
en-59