Bartec R3 Series Operating Instructions Manual page 40

Table of Contents

Advertisement

Operation
36
S
65.0
ER
21.0
D
°C
HA
0
Ambient temperature alarm
As soon as the inside temperature of the radiation sensor exceeds the
defined value, the temperature display will start flashing and the analogue
output will switch to the programmed state (see fault current).
Display
S
Minimum value
20.0 (corresponds to 68 °F)
Maximum value
70.0 or 125.0
(corresponds to 158.0 or 257.0°F)
Increment
0.1 °C
Default value
Sensor-related: 65.0 or 125.0 °C
Fault current
This is where you define what current is to be output via the analogue output
in the event of a fault.
The current is set in mA.
Display
ER
Minimum value
3.9
Maximum value
21.5
Increment
0.1
Default value
21.0
Unit of measurement
You can choose °C or °F as the unit of measurement for the temperature
display.
Display
D
Minimum value
°C
Maximum value
°F
Default value
°C
®
HART
address
You can operate up to 15 transmitters in parallel (multidrop mode). Each
sensor (transmitter) then requires an individual address between 1 and 15.
The address must be set to 0 if you want to operate the transmitter in
standalone operation (point-to-point operation).
Display
HA
Minimum value
0
Maximum value
15
Increment
1
Default value
0
Operating Instructions Radiation sensors R3XX