03/2009
Cause:
The monitoring time for the configuration has expired.
Fault value (r0949, interpret decimal):
0: The transfer time of the send configuration data has been exceeded.
1: The transfer time of the receive configuration data has been exceeded.
Remedy:
Check communication line.
208501
<location>COMM BOARD: Monitoring time process data expired
Message
-
value:
Drive object:
A_INF, B_INF, CU_LINK, CU_S, HUB, S_INF, SERVO, TB30, TM15, TM15DI_DO, TM17, TM31,
TM41, TM54F_MA, TM54F_SL, VECTOR
Reaction:
A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF3 (IASC/DCBRAKE, NONE, OFF1, OFF2, STOP1, STOP2)
VECTOR: OFF3 (IASC/DCBRAKE, NONE, OFF1, OFF2, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The set monitoring time expired while transferring process data via COMM BOARD.
See also: p8840 (COMM BOARD monitoring time)
Remedy:
- check communications link.
- check the set monitoring time if the error persists.
See also: p8840 (COMM BOARD monitoring time)
208502
<location>COMM BOARD: Monitoring time sign-of-life expired
Message
-
value:
Drive object:
A_INF, B_INF, CU_LINK, CU_S, HUB, S_INF, SERVO, TB30, TM15, TM15DI_DO, TM17, TM31,
TM41, TM54F_MA, TM54F_SL, VECTOR
Reaction:
A_INFEED: OFF1 (OFF2)
SERVO: OFF1 (OFF2, OFF3)
VECTOR: OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the sign-of-life counter has expired.
The connection to the COMM BOARD was interrupted.
Remedy:
- check communications link.
- check COMM BOARD.
208504
<location>COMM BOARD: Internal cyclic data transfer error
Message
%1
value:
Drive object:
A_INF, B_INF, CU_LINK, CU_S, HUB, S_INF, SERVO, TB30, TM15, TM15DI_DO, TM17, TM31,
TM41, TM54F_MA, TM54F_SL, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic actual and/or setpoint values were not transferred within the specified times.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
Check the parameterizing telegram (Ti, To, Tdp, etc.).
208510
<location>COMM BOARD: Send configuration data invalid
Message
%1
value:
Drive object:
A_INF, B_INF, CU_LINK, CU_S, HUB, S_INF, SERVO, TB30, TM15, TM15DI_DO, TM17, TM31,
TM41, TM54F_MA, TM54F_SL, VECTOR
Reaction:
A_INFEED: OFF1 (OFF2)
SERVO: OFF1 (OFF2, OFF3)
VECTOR: OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
COMM BOARD did not accept the send-configuration data.
Fault value (r0949, interpret decimal):
Return value of the send-configuration data check.
© Siemens AG 2009 All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
Overview of Alarms
SINAMICS-Alarms
2-819