CLIMATE PROFILES
LED Climate Profiles
STEP
colour
LED 1,2,.., n (n=2,...7) ON:
1...8
green
Climate profile consisting of 2,3,..,7 STEPS
STEP 1,2,.., n completed successfully
Climate profile consisting of 1 or 8 STEPs:
Climate profile completed successfully
EWHT800LX manages curing cycles by means of climate profiles consisting of 8 STEPS.
Each STEP is defined by a set of 10 parameters.
The parameters determine STEP activation delays, duration, type of humidity and temperature regu-
lation, setpoint for regulation, activation of relay AUX1/2 and procedures for completing one STEP
and switching to the next.
By default, regulation is disabled and the setpoints are all zero. The auxiliary relay is enabled
The climate profile START or STOP command is activated by briefly pressing the START/STOP RESET
key (E).
The climate profile RESET command is activated by pressing and holding the START/STOP RESET key
(E).
Example
3-STEP climate profile and temperature/humidity regulation in Neutral Zone mode. The first STEP
starts with a delay while the others start on completion of the previous STEP. The Humidity Setpoint
is fixed whereas the Temperature Setpoint is variable.
Temperature / Humidity
9 - EN
ON
individual LED ON:
STEP in progress
ALL LEDs ON:
db 1/2
Set Point
TemperatureA
db 1/2
db 1/2
Set Point
TemperatureB
db 1/2
Active temperature
regulator
db 1/2
Set Point
Humidity
db 1/2
Active humidity
Endurance 1
Delay 1
regulator
Step1
BLINKING
individual LED:
duty cycle (STEP) not started
Note: only one LED can be
blinking
Step 1
End Mode
Endurance 3
Endurance 2
Step2
Step3
OFF
individual LED:
duty cycle (STEP) not started
ALL LEDs OFF:
climate profile ready to start
individual LED: cycle STOPPED
Time
EWHT800LX