TECHNICAL DATA

DESCRIPTION
Front panel
Container
Dimensions
Mounting
Connections
Operating temperature
Storage temperature
Operating and storage humidity
Display range
Analogue Inputs
Digital inputs
Relay outputs
Analogue Output
Analogue Output Table
Buzzer
Serials
Accuracy
Resolution
Power draw
Power supply
WARNINGS
Important! Make sure the machine is switched off before working on the electrical connections.
The instrument is equipped with:
• Removable screw terminals: for connecting electric cables of 2.5 mm
tion (one wire per terminal in the case of power connections): for the capacity of the terminals, see the label
on the instrument. The relay outputs are voltage free: they are indicated on the board with the letters COM for
Common, NO for Normally Open and NC for Normally Closed contact. When current exceeds 8A on relay out-
puts, 2 x 2.5mm
cables (2 fastons) must be run out for each individual contact to ensure the temperature of the
2
cables does not exceed 85°C.
• Fastons: single row of fastons in series. Do not exceed the maximum permitted current; for
higher loads, use a contactor with sufficient power capacity. Make sure that power supply is of the correct voltage
for the instrument.
Probes have no connection polarity and can be extended using a normal bipolar cable (note that the extension
of the probes influences the instrument's electromagnetic compatibility (EMC): take great care with the wiring).
Probe cables, power supply cables and the TTL serial cables should be routed separately from power cables.
13 - EN
wall mounting (centre distance of holes A-B 181.0 mm; holes C-D 196.5 mm. See Mechanical Installation paragraph)
• removable screw terminals for serial port RS-485, digital and analogue inputs
• removable screw or FASTON terminals for power supply and digital relay outputs (see Wiring Diagrams)
internal housing for door lock disconnecting switch, remote control switch, etc.
WARNING: do not exceed the amperage limits specified on the door lock disconnector markings
• –50...110 °C (NTC) / -55...150°C (PTC) without decimal point, on display with 3 digits + sign
• 4 NTC inputs . PTC selectable by parameter H00
4 voltage-free digital inputs configurable by parameters H11...H14
• OUT1 output SPST 1/2HP 8(4)A 250Va
• OUT2 output SPST 1/2HP 8(4)A 250Va
• OUT3 output SPST 1/2HP 8(4)A 250Va
• OUT4 output SPST 2HP 12(12)A 250Va
Type
Start of
scale range
PWM
-
0...20mA
0
4...20mA
4
0-10V
0
Digital output
-
• 1 TTL port for connection to Copy Card
• 1 TTL port for connection to TelevisSystem
NTC, PTC: 0,1 °C full range • 4...20mA : 1 digit (ndt = 0) / 0.1 digit (ndt=1)
IP54
Bayblend FR 110
front 210x245mm, depth 90mm
-5°C...+50°C
-20°C...+85°C
10..90% RH non-condensing
• 0...2000 (4...20mA)
• 1 current input 4...20mA
1 configurable analogue output
Full scale
Resolution
range
-
1% e.o.s.
20
20
0.1% e.o.s.
10
-
only on models where this is provided
• 1 RS-485 serial port for connection to TelevisSystem
(use with optional plug-in module)
better than 0.5% of end of scale +1 digit
15W
100-240Va ± 10% 50/60Hz
maximum cross-sec-
2
• OUT5 output SPST 1HP 8(8)A 250Va
• OUT6 output SPDT 1/2HP 8(4)A 250Va
• OUT7 output SPDT 1HP 8(8)A 250Va
• OUT8 output SPST 1HP 8(8)A 250Va
Accuracy
Permissible
load
500 Ohm
±1% e.o.s.
500 Ohm
55mA minimum load
resistance 180 Ohm
EWHT800LX