Maximum operating pressure 175 psi 12 bar maximum flow 500 gpm 2000 lpm
Table of Contents

Advertisement

To protect the gears from overload, the oscillating mechanism will
disengage if sufficient force is applied to either side of the oscillator
outlet. The green START KNOB will pop up to indicate the
mechanism is disengaged. See the instructions above to engage
the drive mechanism.
Oscillation speed: The chart shows how many times per minute
the oscillator makes one complete cycle as a function of flow. The
higher the flow, the faster it oscillates.
61m
53m
45m
38m
30m
22m
15m
COVERAGE AREA OF BLITZFIRE OSCILLATING UNIT

7.0 STORAGE

The monitor may be stored pre-connected to its hose on the optional storage bracket, TFT part number XX-B. The storage bracket
may be mounted on a horizontal surface, or a vertical surface with the nozzle end pointing up or sideways. Mounting instructions
are included with the bracket.
WIDTH OF COVERAGE
200'
175'
150'
125'
100'
75'
50'
0'
APPROXIMATE
CYCLES/MIN
BLITZFIRE OSCILLATION SPEED
150' / 45m
125' / 38m
100' / 30m
75' / 23m
50' / 15m
13
GPM
8
175
13
250
21
375
28
500
500 GPM / 1892 Lpm
400 GPM / 1514 Lpm
300 GPM / 1135 Lpm
200 GPM / 757 Lpm
100 GPM / 378 Lpm
20 DEGREES
30 DEGREES
40 DEGREES
FLOW @ 100 PSI / 7 BAR
L/MIN
650
1000
1500
2000