Download Print this page

Emerson LX Series User Manual page 26

Brushless servo drives, amplifier/motor

Advertisement

3.4.3 Transformer Fusing
The secondary of the transformer must have fuses installed in each of the legs. The
current for each fuse is:
Ampere = 0.8 transformer VA rating / RMS secondary voltage
If more than one drive is connected to the same secondary winding, each drive must
have it's own set of fuses as shown in Figure 3-6.
See Table 3-A for the recommended fuse size and type.
3.4.4 External Disconnect
The following two circuits are given as Emerson EMC recommended disconnect /
transformer / fusing examples.
Figure 3.7
Typical disconnect with transformer
Section 3– Page 7
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com

Advertisement

loading