Installation Of The Decoration Panel; Field Setting - Daikin FCQ20EAVAK Installation Manual

Split system air conditioner, ceiling mounted multi flow cassette type
Table of Contents

Advertisement

Available languages

Available languages

Wiring Method (See "8. ELECTRIC WIRING WORK''.)
(3) Remove the control box lid
(4) Add remote controller 2 (slave) to the terminal block for remote controller (P1, P2) in the control
box. (There is no polarity.)
Remote
controller 1

9. INSTALLATION OF THE DECORATION PANEL

<Read ''11. TEST OPERATION'' before making a test operation without attaching the decorated panels.>
• Refer to the installation manual attached to the decoration panel.
• After installing the decoration panel, ensure that there is no space between the unit body and decoration
panel.
• When making a test operation before installation of the decoration panel, be sure to check the operation
of the swing flap after the installation.

10. FIELD SETTING

CAUTION
When performing field setting or test operation without attaching the decoration panel, do not
touch the drain pump. This may cause electric shock.
• Be sure to check that the outdoor unit has been wired.
• Make sure the control box lids are closed on the indoor and outdoor units.
• Field setting must be made from the remote controller and in accordance with installation conditions.
• When using wireless remote controllers, wireless remote controller address setting is necessary. Refer to
the installation manual attached to the wireless remote controller for setting instructions.
• Setting can be made by changing the "Mode No", "FIRST CODE NO." and "SECOND CODE NO.".
• For setting and operation, refer to the "FIELD SETTING" in the installation manual of the remote controller.
• Do not set numbers unless mentioned in the table.
10-1 Setting ceiling height
• Select the SECOND CODE NO. that corresponds to the ceiling height "Table 3".
(SECOND CODE NO. is factory set to "01".) Table 3
Table 3
Standard · All
round outlet
Ceiling
height (m)
High ceiling 1
High ceiling 2
NOTE
1. "Mode No." setting is done in a batch for the group. To make or confirm settings for an individual unit,
set the internal mode number in parentheses.
2. The figure of the ceiling height is for the all round outlet.
3. Do not set numbers unless mentioned in the table.
English
Outdoor unit
Remote
controller 2
FCQ
20·24
36·45
type
type
≥ 2.7
≥ 3.2
2.7 - 3
3.2 - 3.6
3 - 3.5
3.6 - 4.2
Terminal for remote
controller wiring
Remote
Remote
controller 2
controller 1
(Slave)
(Master)
Mode No.
Note) 1
13 (23)
Fig. 35
FIRST
SECOND
CODE NO.
CODE NO.
01
0
02
03
22

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcq36eavakFcq45eavakFcq24eavak

Table of Contents