Dip-Switch Configuration Interface - Intesis IntesisBox FJ-AC-MBS-1 User Manual

Modbus rtu
Table of Contents

Advertisement

ModBus RTU – Fujitsu
®
IntesisBox

DIP-switch Configuration Interface

All the configuration values on FJ-AC-MBS-1 can be written and read from Modbus interface. Otherwise, some of
them can also be setup from its on-board DIP-switch interface.
The device has DIP-switches SW1, SW2 and SW3 on the following locations:
SW2
The following tables apply to the interface´s configuration through DIP-switches:
SW1 – AC configuration + Modbus baud rate
SW1-P1...5
Description
ON
Follower (default
value)
ON
Header
ON
Outdoor Demand rate deactivated
ON
Outdoor Demand rate deactivated (default value)
ON
Rotation and backup deactivated (default value)
ON
Rotation and backup activated
ON
Not used (default value)
ON
Not used
SW2 – Modbus Slave address + Degrees/tenths of degrees (x10) + Temp. magnitude (ºC/ºF)
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
®
IntesisBox
is a registered trademark of Intesis Software SLU
IntesisBox
FJ-AC-MBS-1
L1 L2
SW1
AC Configuration
SW1-P1...5
ON
ON
Table 4.1 SW1: AC Configuration + Modbus baud rate
SW3
ON
B A SG
1 2 3 4 5 6 7 8
EIA 485
SW2
®
*Consider OFF as
AC Unit
ON
1 2 3 4 5 6 7 8
SW1
AC Unit
Description
Low Power mode
(default value)
High Performance
Mode
User Manual r1.0 EN
ON
1 2 3
SW3
Modbus Baud rate
SW1-P6..8
Description
ON
2400bps
ON
4800bps
ON
9600bps (Default
value)
ON
19200bps
ON
38400bps
ON
57600bps
ON
76800bps
ON
115200bps
URL
http://www.intesisbox.com
EmailP
info@intesisbox.com
hone
+34 938047134
12/21