Read / Write Variables - Ebmpapst EC-FAN Operating Manual

Table of Contents

Advertisement

Pa
7.7

READ / WRITE VARIABLES

Register Number Fan 1
Fan Address
Speed Input
Ramp Up
Ramp Down
Maximum Speed
Actual Speed
DC Link Voltage
DC Link Current
Input Power
Table 1 Read and Write variale registers
Figure 20 describes the "Read and Write" type variables for the first MODBUS fan (Fan 1) in an installation. Take note that
each MODBUS fan has 30 registers assigned on the EC-Fan Gateway device.
Please apply the formula found under Register Number Fan (X) to determine the appropriate register number for the
different variables that represent Fan2,3 ... 31. For example, if you were to change the "Ramp Up" time on Fan 2 then you
will be writing a value at register 43 (30(2-1)+13 = 43). Subsequently, the "Ramp Up" time for Fan 3 is assigned to register
73.
Take note that if the address is changed digitally via the building management system, this address change will also have
to be implemented on the EC-Fan Gateway device.
Once the above steps are completed your EC-FAN GATEWAY has been successfully set up.
If you have further questions please contact your ebm-papst representative or your nearest ebm-papst office.
ebm-papst A&NZ Pty Ltd
10 Oxford Road · Laverton North VIC 3026 · Phone +61 (03) 9360 6400 · Fax +61 (03) 9360 6464
ABN 33 115 927 556
NSW Phone +61 (02) 9827 6400 · NSW Fax +61 (02) 9827 6464 · NZ Phone +64 (09) 525 0245 · NZ Fax +64 (09) 525 0246
sales@ebmpapst.com.au · www.ebmpapst.com.au
Register Number Fan (X)
1
5
13
14
(30(x-1)+ Register
Number Fan 1)
12
19
21
22
23
Register Type
Comments
Write Values
Write Values
Write Values
Write Values
Take note all
variables are at a
Factor of 0.1
Read Only
Read Only
Read Only
Read Only
Page 12 of 15