Checks to be carried out prior to installation.................... 13 Electrical connection ............................ 14 Commissioning/Start-up/Shutdown.................... 16 Commissioning/Start-up .......................... 16 Shutdown................................ 17 Returning to service ............................ 17 Servicing/Maintenance ........................ 18 Maintenance .............................. 18 Trouble-shooting.......................... 19 Related Documents .......................... 20 Wiring diagram............................... 20 EU Declaration of Conformity ...................... 21 Index .............................. 22 Hyper 3 of 24...
The serial number uniquely describes the product and is used as identification in all further business processes. In the event of damage, immediately contact your nearest KSB Service centre to maintain the right to claim under warranty. 1.2 Target group This instruction manual is aimed at the target group of trained and qualified specialist technical personnel.
Page 5
In conjunction with one of the signal words this symbol indicates a hazard involving electrical voltage and identifies information about protection against electrical voltage. Machine damage In conjunction with the signal word CAUTION this symbol indicates a hazard for the machine and its functions. Hyper 5 of 24...
– Hazards to persons due to electrical, thermal, mechanical and chemical effects and explosions – Failure of important product functions – Failure of prescribed maintenance and servicing practices – Hazard to the environment due to leakage of hazardous substances Hyper 6 of 24...
In addition to the safety information contained in this manual and the intended use, the following safety regulations shall be complied with: ▪ Accident prevention, health regulations and safety regulations ▪ Explosion protection regulations ▪ Safety regulations for handling hazardous substances ▪ Applicable standards, directives and laws Hyper 7 of 24...
1. On transfer of goods, check each packaging unit for damage. 2. In the event of in-transit damage, assess the exact damage, document it and notify KSB or the supplying dealer and the insurer about the damage in writing immediately.
NOTE Due to certain components it contains, the device is classified as special waste and meets RoHs 2011/65/EC requirements. Once decommissioned, the device must be properly disposed of in accordance with local regulations. Hyper 9 of 24...
Type series Maximum current [A] Maximum current × 10 Example: 11.5 A × 10 = 115 Code number (type series generation) 4.3 Name plate KSB SE & Co. KGaA Johann-Klein-Straße 9 D-67227 Frankenthal Typ: HYPER 26.1 2018w37 UE: 3/N/PE AC 400 V 50/60 Hz IE: 1,8 - 2,6 A...
▪ 8,0 ▪ 11,5 Nominal insulation voltage V [V AC] Control voltage V [V AC] Enclosure P [kW] IP 54 Mains type TN-C-S mains Dimensions (L × W × H) [mm] 280 × 90 × 85 Weight [kg] Hyper 11 of 24...
▪ Motor protection relay ▪ Colour-coded LED display ▪ Terminal strip for sensor connection 4.8 Accessories ▪ Float switch, circuit open in upper float position ▪ Float switch, circuit closed in upper float position ▪ Dry running protection Hyper 12 of 24...
▪ Installation in potentially explosive atmospheres is not permitted. Ambient conditions The ambient conditions specified in the following table must be observed: Table 8: Ambient conditions Characteristic Value Temperature during operation -10 °C to +50 °C Relative humidity Non-condensing Installation altitude 1000 m above MSL (max.) Hyper 13 of 24...
4. Connect the control unit in accordance with the wiring diagram. (ð Section 9.1, Page 20) 5. Set the motor protection relay to the rated current. 6. Connect the power cable available on site so as to ensure a clockwise rotating field. Hyper 14 of 24...
Page 15
2. Observe the required free cable length of the float switch. 3. The minimum free float switch cable length measured from the antikink bush is 10 cm. 4. Fasten the float switch cable with suitable fasteners. Hyper 15 of 24...
ð To do so briefly set the manual-0-automatic selector switch to manual (only if the water level is above the start-up level) and check the direction of rotation indicator (LED). 7. Set the manual-0-automatic selector switch to automatic. Hyper 16 of 24...
3. Prior to any work on the control unit, use a voltmeter to verify that all phases are dead. 6.3 Returning to service For returning the equipment to service, observe the sections on commissioning/start- up (ð Section 6.1, Page 16) . Hyper 17 of 24...
- Phase failure Check power cable. ✘ Float switch is stuck. Release and check for free movement. ✘ Incorrect pump selection Have it checked by KSB service. ✘ Manual-0-automatic selector switch is set to Set the manual-0-automatic selector switch to manual. automatic.
10 EU Declaration of Conformity 10 EU Declaration of Conformity Manufacturer: KSB SE & Co. KGaA Johann-Klein-Straße 9 67227 Frankenthal (Germany) The manufacturer herewith declares that the product: Hyper Serial number range: 2018w44 bis 2019w52 ▪ is in conformity with the provisions of the following Directives as amended from time to time: –...