Thermistor Motor Protection; Motor Protection Trip Test - Siemens SIRIUS 3RW30 Manual

Industrial controls
Hide thumbs Also See for SIRIUS 3RW30:
Table of Contents

Advertisement

13.5

Thermistor motor protection

(Optional for 3RW402. to 3RW404. with 24 V AC/DC rated control voltage)
Thermistor motor protection
After removing the copper jumper between T11/21 and T22, you can connect and evaluate
either a Klixon thermistor integrated in the motor winding (at terminal T11/T21-T22) or a type
A PTC (at terminal T11/T21-T12).
13.6

Motor protection trip test

TEST / RESET button
You initiate a motor overload trip by pressing the RESET / TEST button for longer than five
seconds. The SIRIUS 3RW40 soft starter is tripped by the fault signal at the OVERLOAD
LED, the FAILURE / OVERLOAD contact 95-98 closes, and the motor that is connected and
running is switched off.
SIRIUS 3RW30 / 3RW40
Manual, 10/2018, NEB535199502000/RS-AB/005
Commissioning
13.5 Thermistor motor protection
121

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirius 3rw40

Table of Contents