Daikin FXLQ-M Series Engineering Data page 9

Floor standing type/concealed floor standing type
Table of Contents

Advertisement

EDUS391502-F7
Concealed Floor Standing Type
Model
Power supply
1 3 Cooling capacity
2 3 Heating capacity
Casing color
Dimensions: (H×W×D)
Rows×Stages×FPI
Coil (Cross
fin coil)
Face area
Model
Type
Motor output
Fan
Airflow rate (H/L)
Drive
Temperature control
Sound absorbing thermal insulation material
Air filter
Liquid pipes
Piping
Gas pipes
connections
Drain pipe
Weight
4 Sound pressure level (H/L)
Safety devices
Refrigerant control
Connectable outdoor unit
Standard accessories
Drawing No.
Notes:
1. Nominal cooling capacities are based on the following conditions:
Return air temperature: 80.0°FDB (26.7°CDB), 67.0°FWB (19.4°CWB)
Outdoor temperature: 95.0°FDB (35.0°CDB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
2. Nominal heating capacities are based on the following conditions:
Return air temperature: 70.0°FDB (21.1°CDB).
Outdoor temperature: 47.0°FDB (8.3°CDB), 43.0°FWB (6.1°CWB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. Anechoic chamber conversion value, measured under JIS conditions. During actual operation,
these values may be higher as a result of installation conditions.
5. Refer to Electric Characteristics for the power input.
FXLQ-M / FXNQ-M
FXNQ18MVJU9
1 phase, 60Hz, 208/230V
Btu/h
18,000 (5.3)
(kW)
Btu/h
20,000 (5.9)
(kW)
Galvanized steel plate
in.
24×53-1/8×8-5/8 (610×1,350×220)
(mm)
3×14×17
ft² (m²)
3.04 (0.282)
2D14B20
Sirocco fan
W
cfm
490/380 (14/11)
(m³/min)
Direct drive
Microprocessor thermostat for cooling and heating
Glass fiber/urethane foam
Resin net (with mold resistant)
in.
φ1/4 (φ6.4) (Flare connection)
(mm)
in.
φ1/2 (φ12.7) (Flare connection)
(mm)
in.
φ27/32 (φ21) O.D (Vinyl chloride)
(mm)
lbs (kg)
69 (31)
dB (A)
Thermal protector for fan motor
Electronic expansion valve
R410A VRV series
Operation manual, Installation manual, Insulation for fitting,
Drain hose, Clamps, Screws, Washers, Level adjustment
screw
35
40/35
Fuse,
Operation manual, Installation manual, Insulation for fitting,
Drain hose, Clamps, Screws, Washers, Level adjustment
screw
C: 3D045648A
Specifications
FXNQ24MVJU9
1 phase, 60Hz, 208/230V
24,000 (7.0)
27,000 (7.9)
Galvanized steel plate
24×53-1/8×8-5/8 (610×1,350×220)
3×14×17
3.04 (0.282)
2D14B20
Sirocco fan
35
560/420 (16/12)
Direct drive
Microprocessor thermostat for cooling and heating
Glass fiber/urethane foam
Resin net (with mold resistant)
φ3/8 (φ9.5) (Flare connection)
φ5/8 (φ15.9) (Flare connection)
φ27/32 (φ21) O.D (Vinyl chloride)
69 (31)
41/36
Fuse,
Thermal protector for fan motor
Electronic expansion valve
R410A VRV series
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents