Specifications
2.2

FXNQ

Concealed Floor Standing Type
Model
Power supply
1 3 Cooling capacity
2 3 Heating capacity
Casing color
Dimensions: (H×W×D)
Rows×Stages×FPI
Coil (Cross
fin coil)
Face area
Model
Type
Motor output
Fan
Airflow rate (H/L)
Drive
Temperature control
Sound absorbing thermal insulation material
Air filter
Liquid pipes
Piping
Gas pipes
connections
Drain pipe
Weight
4 Sound pressure level (H/L)
Safety devices
Refrigerant control
Connectable outdoor unit
Standard accessories
Drawing No.
Notes:
1. Nominal cooling capacities are based on the following conditions:
Return air temperature: 80.0°FDB (26.7°CDB), 67.0°FWB (19.4°CWB)
Outdoor temperature: 95.0°FDB (35.0°CDB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
2. Nominal heating capacities are based on the following conditions:
Return air temperature: 70.0°FDB (21.1°CDB).
Outdoor temperature: 47.0°FDB (8.3°CDB), 43.0°FWB (6.1°CWB)
Equivalent ref. piping length: 25ft (7.6m) (Horizontal)
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. Anechoic chamber conversion value, measured under JIS conditions. During actual operation,
these values may be higher as a result of installation conditions.
5. Refer to Electric Characteristics for the power input.
6
FXNQ07MVJU9
1 phase, 60Hz, 208/230V
Btu/h
7,500 (2.2)
(kW)
Btu/h
8,500 (2.5)
(kW)
Galvanized steel plate
in.
24×36-5/8×8-5/8 (610×930×220)
(mm)
3×14×17
ft² (m²)
1.71 (0.159)
D14B20
Sirocco fan
W
15
cfm
245/210 (7/6)
(m³/min)
Direct drive
Microprocessor thermostat for cooling
and heating
Glass fiber/urethane foam
Resin net (with mold resistant)
in.
φ1/4 (φ6.4) (Flare connection)
(mm)
in.
φ1/2 (φ12.7) (Flare connection)
(mm)
in.
φ27/32 (φ21) O.D (Vinyl chloride)
(mm)
lbs (kg)
47 (21)
dB (A)
35/32
Fuse,
Thermal protector for fan motor
Electronic expansion valve
R410A VRV series
Operation manual, Installation manual,
Insulation for fitting, Drain hose, Clamps,
Screws, Washers, Level adjustment
screw
FXNQ09MVJU9
1 phase, 60Hz, 208/230V
9,500 (2.8)
10,500 (3.1)
Galvanized steel plate
24×36-5/8×8-5/8 (610×930×220)
3×14×17
1.71 (0.159)
D14B20
Sirocco fan
15
245/210 (7/6)
Direct drive
Microprocessor thermostat for cooling
and heating
Glass fiber/urethane foam
Resin net (with mold resistant)
φ1/4 (φ6.4) (Flare connection)
φ1/2 (φ12.7) (Flare connection)
φ27/32 (φ21) O.D (Vinyl chloride)
47 (21)
35/32
Fuse,
Thermal protector for fan motor
Electronic expansion valve
R410A VRV series
Operation manual, Installation manual,
Insulation for fitting, Drain hose, Clamps,
Screws, Washers, Level adjustment
screw
C: 3D045648A
EDUS391502-F7
FXNQ12MVJU9
1 phase, 60Hz, 208/230V
12,000 (3.5)
13,500 (4.0)
Galvanized steel plate
24×42-1/8×8-5/8 (610×1,070×220)
3×14×17
2.15 (0.200)
2D14B13
Sirocco fan
25
280/210 (8/6)
Direct drive
Microprocessor thermostat for cooling
and heating
Glass fiber/urethane foam
Resin net (with mold resistant)
φ1/4 (φ6.4) (Flare connection)
φ1/2 (φ12.7) (Flare connection)
φ27/32 (φ21) O.D (Vinyl chloride)
56 (25)
36/33
Fuse,
Thermal protector for fan motor
Electronic expansion valve
R410A VRV series
Operation manual, Installation manual,
Insulation for fitting, Drain hose, Clamps,
Screws, Washers, Level adjustment
screw