Selecting the Primary Measuring Device (P600)
The MultiRanger 200 supports the following primary measuring devices to calculate the flow rate based on either the Absolute
method or Ratiometric method. The design standards of these devices are programmed in the MultiRanger 200, and it applies the
correct standard formula to calculate the flow.
If you do not have a primary device, or your primary devices are not included in this list, selecting
Calculation
Universal Curved Flow Calculation
or
method.
Parameter
Parameter Index
G
P600
(dual channel 1 or
2, if both enter 00)
Select one value from the following list of primary measuring devices and methods per channel application.
Value
0
Flow calculation is off and no flow rate or total flow will be calculated
1
Exponential devices
2
Palmer-Bowlus Flume
3
H-Flume
4
Universal Linear Flow Calculation
5
Universal Curved Flow Calculation
6
BS-3680/ISO 4359 Rectangular Flume
7
BS-3680/ISO 1438/1 Thin Plate V-notch Weir
Configuring for the Selected Measurement Devices
The following sections present the calculations required to set the parameter values necessary to configure the applications
according to the measuring device.
Section 1.0 Exponential Device (P600 = 1)
Single exponent devices supported by MultiRanger 200:
Standard Weirs
V-notch or triangular
Rectangular or Suppressed
Trapezoidal or Cipolleti
MultiRanger 200 and Flow Configuration
enables the MultiRanger 200 to calculate the flow rate based on Ratiometric
Value
Choose from 0 through to 7
Description of Selected Value
Flumes
Parshall
Leopold Lagco
Cut Throat
AG040303

APPLICATION GUIDE

Universal Linear Flow
Flow Calculation Method
Other
any other single exponent
primary measuring device,
whose exponent value is
known.
None
Ratiometric
Ratiometric
Ratiometric
Ratiometric
Ratiometric
Absolute
Absolute
2 of 10