Table 8

Torque specifications, general
Electrical Connections
with 1 Belleville Washer
Torque
lb-in
3/8 / M10
120
1/2 / M12
240
Input and Output Breakers
Up to 150 amp
80
175 - 500A
120
Table 9
Panelboard main circuit breaker torque specifications
Torque
lb-
in
Busbar-to-Breaker
240
Table 10
Branch circuit breaker torque specifications
Breaker Size
lb-in
Up to 30 amp
35
40 to 100 amp
45
Table 11
Terminal block compression lug torque specifications
Torque
AWG Wire Size
or Range
lb-in
#14 - #10
35
#8
40
Vertiv
| Liebert
Distribution Cabinet
®
Electrical Connections
with 2 Belleville Washers
Torque
N-m
lb-in
13.6
240
27.1
480
9.0
160
13.6
240
N-m
27.1
N-m
4.0
5.1
N-m
4.0
4.5
for Liebert EXM
N-m
27.1
54.2
18.0
27.1