Figure 15 Typical Liebert EXM 880mm Distribution Cabinet equipment arrangement

47.2" (1200mm)
Battery Cabinet #1
NOTES
1. All dimensions are in inches (mm).
2. 24" (610mm) minimum clearance above the unit for ventilation.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
Remove, punch to suit conduit and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. All wiring must be in accordance with national and local electrical codes.
8. All battery cabinets must be positioned on the left side of the UPS.
Vertiv
| Liebert
Distribution Cabinet
®
127.2" (3228mm)
32.9"
(840mm)
UPS
MBC
FRONT VIEW
for Liebert EXM
User Manual |
11.8" (300mm)
34.6" (880mm)
(2000mm)
Distribution Cabinet
EXM43016
Rev. 0
78.7"
21