Figure 3
Recommended minimum front and top clearances
NOTE
Service access is required at the front.
Table 3
Liebert EXM Distribution Cabinet heat output
Full Load Heat Output
Unit kVA
BTU/Hr (kW)
50
4700 (1.37)
100
8300 (2.43)
150
11,600 (3.39)
200
15,500 (4.45)
250
18,400 (5.39)
2.2
Power and Control Wiring
Power and control wiring should be installed by licensed electricians. All power and control wiring
must comply with the NEC and applicable local codes.
Input power connections are always to be fed from the Liebert EXM UPS. Either attached using
factory-provided cables or remotely using cables provided by others.
Vertiv
| Liebert
Distribution Cabinet
™
®
18" (457mm)
Front
(914mm)
for Liebert EXM
User Manual |
™
™
36"
8