Figure 14 Typical Liebert EXM 600mm Distribution Cabinet equipment arrangement

34.6" (880mm)
Battery
Cabinet #1
NOTES
1. 18" (457mm) minimum clearance above unit for ventilation.
2. Keep cabinet within 15 degrees of vertical.
3. Cable Entry
UPS: Bottom cable entry through removable plates
MBC: Top and bottom entry through removable plates
Remove, punch to suit conduit size and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wiring must be run in separate conduits.
6. All wiring is to be in accordance with national and local electrical codes.
7. All battery cabinets must be positioned on the left side of the UPS.
Vertiv
| Liebert
Distribution Cabinet
®
94" (2388mm)
23.6"
(600mm)
UPS
MBC
FRONT
for Liebert EXM
User Manual |
11.8"
(300mm)
23.6"
(600mm)
78.7"
(2000mm)
Distribution
Cabinet
20