Safety 1.1 Intended Use ® The CONTOIL flow meter is designed and solely intended for the flow measurement of Diesel oil to Heavy Fuel Oil according to ISO 8217-2010 Improper or non-intended use may lead to the operational reliability of the device and is no longer guaranteed.
Page 3
1.3 Safety rules and precautionary measures The manufacturer accepts no responsibility if the following safety rules and precautions are disregarded. Modifications of the device implemented without preceding written consent from the manufacturer, will result in the immediate termination of product liability and warranty period.
Product description 2.1 Scope of supply 1 Flow meter with mechanical counter. 1 mounting and operating instruction (this manual) 2.2 Flow meter configuration ® The CONTOIL flow meters consist of a hydraulic part, a coupling and an mechanical counter. The hydraulic part determines the nominal size of the flow meter. The flow meters are calibrated before they leave the factory.
Page 5
2.4 Return of materials Never send a device/system back if you are not absolutely certain that all traces of hazardous substances have been removed, e.g. substances which have penetrated crevices or diffused through plastic. Costs incurred for waste disposal and injury (burns, etc.) due to inadequate declara- tion and/or cleaning will be charged to the delivering company or the operator.
Installation CAUTION The surfaces of the device and the medium may be hot. Risk of burns! Carry out work only on cooled systems. Work may only be performed by authorized specialists in accordance with the applicable regulations. Use appropriate protective equipment. WARNING The pipe and the device may be under pressure.
Page 7
3.1 Mounting Flow meter installation Easy access for reading the flow meter and controlling the ancillary equipment is important. Provided that the arrow on the housing is in the direction of flow, the flow meter can be installed in any position without any special modifications. The mechanical counter can be turned to the desired position Exception: upside down installation.
Page 8
Correct layout of flow meter and accessories If the flow meter is used for viscosities higher than 5 mPa.s, or if it is mounted on the suction side of a pump, the pressure loss and the flow rate that can still be attained should be deter- mined with the help of the pressure loss curves provided in CONTOIL®...
Page 9
Dirt filter, Safety filter Filters should be fitted to prevent any damage to the flow meter from impurities in the oil. Maximum mesh width for filters Nominal Flow meter type size VZOA DN15 0.250mm 0.100mm DN20 0.400mm 0.100mm DN25 0.400mm 0.250mm DN40 0.600mm...
Page 10
Special requirements - differential measurements For differential measurements, one flow meter is installed in the supply line pipe and one in the return line pipe. The flow difference between these meters determines the consumption. If ordered with the "differential measurement" option, VZOA flow meters are calibrated in ac- cordance with the indicated supply and return flow volumes.
Page 11
Installation of the flow meter on the suction side of a pump If the flow meter is installed on the suction side of a pump, consideration must be given to avoid air-intake or foam. Filter Flow meter on suction side Pump Installation of the flow meter on the pressure side of a pump Filter...
Page 12
3.2 Mechanical installation WARNING Leakage or rupture due to connections being made using force. Risk of severe injury! Risk of substantial property damage! Never attempt to overcome misalignments (lateral, angular, longitudinal, torsional) using force. Make sure the pipings are flexible enough, if not: use compensators. ...
Page 13
Preparing for installation Check flow meters and installation material. Compare the data of the flow meter name plate with the expected maximum conditions of the installation. They may not exceed the flow meter specifications: • Continuous flow rate (Qcont l/h) •...
Page 14
Installing the meter in the pipe Remove the protection plugs or caps from the flow meter (inlet and outlet). Insert the flow meter into the pipeline in the prescribed position and flow direction. The arrow on the flow meter should correspond with the direction of flow. Install mating flanges parallel and without tension in the pipe.
Page 15
3.3 Electrical Installation NOTICE Electrical connection to the supply voltage and / or connections to other systems. Risk of malfunction or damage Review of technical data, chapter 8.1, on page 22. 3.4 Electrical connection Display unit options VZO, VZOA Pulser RV Cable;...
3.5 Engineering notes Parameterizing ancillary devices Some ancillary units require programming of pulse values or frequency (see the relevant operating instructions). Pulse values of the VZO(A) flow meters: see type plates. The maximum frequency is calculated with the following formula: .
Maintenance and Repair 5.1 Calibration All our flow meters are calibrated in the factory. An accuracy check and recalibration is offered at Aquametro Oil & Marine AG, this is usually dependent on customer, operator or regulation requirements. This interval depends largly on the operating conditins, process liquid and the application the flow meter is installed in.
Page 18
Before working on the hydraulics: put the system or section out of operation close the stop valves release the pressure put a suitable tray underneath the connection to be worked on be prepared for spillage, have absorbent at hand Cleaning of flow meter: ...
Page 19
The cleaning and revision cycle depends largely on the conditions of operation. Under favourable conditions 5-10 years suffice. Check the devices for corrosion. Recommended revision cycle Flow meter. Totalizer Volume Time 20‘000 m DN 15 50‘000 m DN 20 100‘000 m DN 25 7 years 300‘000 m...
Troubleshooting ® 6.1 For all CONTOIL flow meter Fault symptoms Possible causes Procedures 1) Pointers on roller This is normal at high flow No action required counter rotate rates and has no effect on irregularly accuracy of measurement ...
Decommissioning, Dismantling and Disposal CAUTION The surfaces of the device/system and the medium may be hot. Risk of burns! Carry out work only on cooled devices/systems. Work may only be performed by authorized specialists in accordance with the applicable regulations. ...
Appendix 9.1 Dimensional drawings Flow meters All flow meters with threaded ends are according to ISO 228-1 DN15, 20, 25: with threaded ends DN40: with threaded ends All flow meters with flanges are according to EN 1092-2, ASME B16.5 or JIS B2220 DN15, 20, 25: with flanged ends DN40, 50: with flanged ends Nomial size...
Page 24
Dimensions of electronic and mechanical counters Sensor VZF(A) II* VZO 15 - 25 VZO 40 - 50 / VZOA 15 - 50 Max. temperature 130/180°C 130°C 180°C 130°C 180°C Pulsers RV IN RV IN Dimensional drawing VZF(A)*, VZO(A) Dimensional drawings (h2) 1 - 7 from table below 9.2 Display of evaluation units VZO/VZOA VZF II / VZFA II*...
Page 25
9.3 Certificates All the below mentioned certificats / approvals, can be found on our web site www.aquametro-oil-marine.com Class Approvals Det Norske Veritas - German Lloyd Norway - Germany Lloyds Register United Kingdom Russian River Register Russian Maritime Register RMRS of Shipping Versions with type approval and metrological CE approval ®...