7 Checking functions

Building Technologies
Fire Safety
The functions must be checked after installation and in accordance with the
maintenance regulations.
NOTICE
Open line of the power supply for external devices
Unwanted automatic service provider notification.
For both function checks, ensure that the alternative power supply is active
respectively.
Check the following functions:
l
1. Display and transmission of a mains fault
2. Display and transmission of a battery fault
Mains fault
1. Disconnect the mains voltage.
2. Check the LED function display on the housing.
3. Check the 'Fault' signal transfer on the fire control panel.
a The 'Fault' LED function display lights up.
a The event 'Fault' is displayed on the fire control panel.
Battery fault
1. Disconnect the batteries.
2. Check the LED function display on the housing.
3. Check the 'Fault' signal transfer on the fire control panel.
a The 'Fault' LED function display lights up.
a The event 'Fault' is displayed on the fire control panel.
Checking functions
7
25 | 32
A6V10393194_d_en_--
2018-11-05