6
Bearing
7
Type of Heat Exchange Tube
8
Serial Number
9
Power Supply

1.3 Product Features

1.3.1 General
It's a kind of integrated DC inverter unit that comprises cooling, heating and water heating functions,
and up to 5.0 energy efficiency. It adopts R32 refrigerant and two-stage compressor. For heating,
ambient temperature range is -25~35℃ while the leaving water temperature range is 25~60℃.
The Versati Ⅲ unit is designed specially for the European market where there is a demand for
high-temperature water. Thanks to the dual-stage compression and enthalpy gain through gas injection,
the heating energy efficiency at low temperature will rise up greatly with the leaving water temperature
up to 60° C. The whole series of products strictly comply with EN14511,EUROVENT energy efficiency
Class A and SCOP class A+++(35℃), SCOP class A++(55℃) with EN14825. Their COP can reach up to
5.0. This unit can realize space heating and sanitary hot water supply through terminal units, like the fan
coil unit, floor coil and radiator. Environment-friendly refrigerant R32 is adopted for the unit, with ODP of
0 and quite low GWP (=675). Besides, the adopted heat pump technologies will reduce consumption of
coal and other energy source and lower greatly CO2 emission. Ranged from 4.0kW~16kW, it is widely
applicable to small and medium-sized apartment, large-sized villa etc.
1.3.2 Features
 Wide Operation Range
Heating: -25~35° C; Cooling: 10~48° C; Water Heating: -25~45° C
 Unique Low-Temp Hi-heat Dual-stage Compressor
1. Under low-temperature conditions, compared with the conventional compressor, the dual-stage
low-temp hi-heat compressor will generate less loss of heat capacity and get higher energy efficiency.
2. Floodback, high discharge temperature and other problems can be completely avoided under
low-temp conditions and the compressor's reliability will be enhanced greatly.
3. Dual-stage compression, dual-stage throttling and intermediate enthalpy adding through gas
injection will raise the leaving water temperature and improve the control accuracy.
 High-efficiency Component(Inverter pump, Inverter fan, Plate heat exchanger)
Engineering Data
Default-Non-bearing water tank;
C-Bearing water tank
Default-No heat exchanger;
J-Inner coil static heating(J-Single coil; J2-Double coils);
JW-Outer coil static heating
A,B,C......
K=220-240V,~,50Hz; M=380-415V,3N~,50Hz; H=380V,3N~,60Hz