1. Controller is not under "auto
mode
2. Voltage of generator power
Generator
output terminal is abnormal
works, but ATS
3. Wiring fault
doesn't transfer
4. F5 fuse on the terminal strip
the load to
X1 melts down.
connect with
5. Inner contactors of KPD100
generator
controller terminal 30、31 are
open.
6. Transfer switch broken
1. Wiring fault
Grid restores
2. F2 fuse on the terminal strip
but ATS
X1 melts down.
doesn't transfer
3. Inner contactors of KPD100
the load to
connect with
grid.
4. Transfer switch broken
Switch
1. Cooling delay time of
transfers the
generator
load but
2.Circuit fault
generator still
3.Controller abnormal
works
1. F1 fuse melt down
Charger does
2. Wiring fault
not work (if
3. Battery charger broken
equipped)
4. Battery worn or broken
"
controller terminal 34、35
are open.。
1.Choose "auto mode
2.Check voltage of output terminal
3.Check wiring between ATS and generator
4. Check F5 fuse, Replace it if broken after trouble
shooting
5.Check closed contactor. Replace KPD100
controller if it is abnormal.
6. If there is rated voltage on two ends of transfer
switch, please replace the switch
1. Check wiring between ATS and generator
2. Check F2 fuse, Replace it if broken after trouble
shooting
3. Check closed contactor. Replace KPD100
controller if it is abnormal.
4. If there is rated voltage on two ends of transfer
switch, please replace the switch
1. Wait until the delay time finishes(≤30 minuets)
2. Check wiring between ATS and generator
3. Check controller, replace it if broken.
1. Replace fuse after troubleshooting
2. Check wiring between ATS and generator
3. Replace battery charger.
4. Replace battery.