Under "AUTO mode
", press of the key
can not start the set.
3.5.3

Normal operation of ATS cabinet

It is necessary to ensure the normal installation and set of ATS cabinet and generator set, correct
wiring of ATS AC circuit and control cables.
Turn on the power switch of KPD100 controller on generator set, press the key
, it will enter into
"auto mode
","Auto indicator lamp" on control panel will be light. Controller will monitor the grid
data( See the following table)
When the data goes to be continuously abnormal, controller will start the generator set and make
ATS cabinet switch to generator set power. KPD100 controller still monitor data of generator set
and grid as well as engine water temperature, oil pressure, oil level to keep generator set work in
normal state. After grid is restored to be normal, controller will work again to connect load to grid
power. Generator set will stop automatically after cooling delay, and keep in standby state.