Regular maintenance

Periodic maintenance can make the transfer switch more reliable
Maintenance should be carried out by professional person. Ask for the dealer to repair or replace
the parts.
AC power may cause electric shock even death. Incorrect installation will cause personal injury and
equipment damage, so all maintenance should be carried out by professional person.
If not all AC power supply are cut off, transfer switch will cause injury .Ensure the switch control
button in the "stop" position. If a battery charge is equipped with, please disconnect the charger and
the starting battery (Disconnect - pole first) before maintenance
The gas generated by battery will burn which has injury hazard. Forbid smoking, electric arcs and
flame during battery maintenance.
1. Cut off all AC power supply
A. Cut off the AC power supply before continuing operation. Turn the generator operation switch
to stop position.
B. Disconnect the battery charge with AC power supply if it is equipped with.
C. Then disconnect the starting battery( Disconnect - pole first)
2. Clean
A. Clean all controller, gages, switches and inner bus and connection chips by a vacuum cleaner
B.Close the case door and clean the external surface by sponge ( mild detergent and water)
Do not let water flow into the case, especially gages, lamps and switches
3. Check
A.Check bus and supporting parts if there are burns, cracks, corrosion as well as any worn
element. Contact dealer to replace these worn parts.
B.Check static contactor and movable contactor. Replace them if worn
C.Check all control wires and cables (especially the wires near door hinge)if they are worn
D.Check all control wires and cables. Fasten them if loose.
E.Check inner parts. Fasten them if loose.
1. Daily maintenance
A.If necessary, fasten the bus, control lines, power cables and terminals as well as all cable
connection chips
2. Connect AC power and check operation
A. Connect starting battery (connect - pole at last), common AC power and activate the power of
generator set controller is equipped with.
B. Check the battery charge and ensure correct operation
C. Close and lock the door according to this chapter