PREMASGARD
The pressure measuring transducer PREMASGARD
into standard signals of 0 -10 V or 4...20 mA. Process connection is G ½ " straight external pipe thread. SHD is used for pressure measurement in
gaseous and liquid media. Applications of this pressure transmitter are in hydraulics, pneumatics, process technology, in mechanical and plant
engineering. The pressure measuring cell is gasketless welded together with the pressure pick-up.
TECHNICAL DATA
Power supply:
Measuring ranges:
Output signal:
Electrical connection:
Pressure connection:
Type of pressure:
Measuring principle:
Temperature of medium:
Mounting:
Enclosure:
Connecting head:
Medium contacting parts:
Response time:
Characteristic line:
Overload range:
Bursting pressure:
Protection class:
Protection type:
Standards:
ACCESSORIES:
Connecting diagram
2
Output pressure 0-10V
3
GND
1
Supply voltage
UB+ 24V AC/DC
®
PREMASGARD
SHD – Pressure measuring transducers, Premium
Type ⁄
Measuring
WG01
Range
SHD - U
S H D - U 1
0...1 bar
S H D - U 2,5
0...2.5 bar
S H D - U 6
0...6 bar
S H D - U 10
0...10 bar
S H D - U 16
0...16 bar
S H D - U 2 5
0...25 bar
S H D - U 4 0
0...40 bar
SHD
®
SHD measures relative pressures in the bar range. It converts the measurand pressure
24 V AC ⁄ DC for output 0 –10 V
7 - 33 V DC for output 4 ... 20 mA
see table (other ranges upon request)
0 -10 V, 3-wire, (working resistance > 10 kOhm) or
4 ... 20 mA, 2-wire, (working resistance < (UB (V) -7 V) ⁄ 0.02 A ;
RL depending on working resistance
plug connector DIN EN 175301-803-A
G ½ " sealing at the back, and manometer (combined) with profile
gasket FPM, special WW G ¼ " DIN 3852
relative
steel measuring cell
– 40...+135 °C
directly on pressure line
stainless steel 1.4305
plastic, approx. 98 x 50 x 34 mm
stainless steel 1.4305
2 ms (1 ms typical)
± 0.3 %
< 6 bar: 5 x of final value
> 6 bar: 3 x of final value (max. 1500 bar)
< 6 bar: 10 x of final value
> 6 bar: 6 x of final value (max. 2500 bar)
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, electromagnetic compatibility according to EN 61 326,
EMC directive 2004 ⁄ 108 ⁄ EC
incl. receptacle DIN EN 175301-803-A
OUT
2
3
1
+
IN
Item No.
U - variant
13 01 - 21 11-052 0-220
13 0 1- 2 111- 0530- 220
13 01 - 2111- 0550- 220
1 30 1 -2 1 11-05 60-220
1 30 1 -2 111- 0570- 220
13 0 1- 2 111- 0580- 220
13 01 - 211 1-0590 -220
SHD - U
Connecting diagram
2
Output pressure 4...20mA
GND
3
Free
1
Supply voltage
UB+ 24V DC
Type ⁄
WG01
SHD - I
S H D - I 1
S H D - I 2,5
S H D - I 6
S H D - I 10
S H D - I 16
S H D - I 2 5
S H D - I 4 0
OUT
2
3
1
+
IN
Measuring
Item No.
Range
I - variant
0...1 bar
1301-2112-0520-120
0...2.5 bar
1301-2112-0530 -120
0...6 bar
1301-2112-0550-120
0...10 bar
1301-2112-0560-120
0...16 bar
1 301-2112-0570-120
0...25 bar
1301-2112-0580-120
0...40 bar
1301-2112-0590-120
Rev. 2016 - V11 GB