Download Print this page

Specifications - Mitsubishi Electric Lossnay LGH-F300RX3-E Operating Instructions

Hide thumbs Also See for Lossnay LGH-F300RX3-E:

Advertisement

Maintenance (Continued)
Assembly after maintenance
1. Bearing in mind the following points, assemble the parts following the
sequence for their removal in reverse.
Align the air filter with the grooves on the Lossnay and holder and
push it in.
When installing the air filters, take care not to damage the exposed
surfaces of the Lossnay cores.

Specifications

Model name
Voltage (V)
LGH-
1-Phase
F300RX
-E
208 - 230
3
LGH-
1-Phase
F470RX
-E
208 - 230
3
1-Phase
LGH-
F600RX
-E
208 - 230
3
1-Phase
LGH-
208 - 230
F1200RX
-E
3
*
The values given in the table for the sound level reflect the levels measured at a position 59 inch immediately below the unit in an anechoic
chamber.
*
The sound at the air outlets is the values at a 45° angle, 59 inch in front of the unit.
*
The above values apply during Lossnay ventilation when the fan speed is set to extra high speed.
*
The values are under 230V 60Hz.
After-sales servicing
Consult with your dealer about the after-sales services provided for this
Lossnay product.
4
Power
Line
Current (A)
consumption
frequency
(W)
(Hz)
60
1.3
278
60
2.5
560
60
2.9
654
60
5.7
1290
MITSUBISHI ELECTRIC CORPORATION
2. Press the filter button on the remote controller (PZ-41SLB-E) two
times in succession.
(This clears the Lossnay's operating time cumulative data.)
Relevant button
FILTER
(Press twice)
Excharge efficiency (%)
Air volume
Static
pressure
Temperature
(CFM)
(in. H
O)
2
300
0.65
69
470
0.96
69
600
0.80
69
1200
0.75
69
If you hear strange sounds, if no air is blown out or if some other
trouble occurs, switch off the power and contact your dealer.
Consult with your dealer concerning the cost of inspection or
repair work.
Relevant display items
FILTER
Sound level (dB(A))
Enthalpy
Below
the unit
outlets
Heating Cooling
62
44
36
62
44
39
50.5
62
44
39
62
44
41
Weight
Air
(Ibs)
44
73
143
47
159
52
395

Advertisement