Control Options

You must enter an Installer Password to access the CONTROL menu from the Main Menu. The
following settings can be changed:
CHANGE
HYSTERESIS
ANTICIPATION TIME
MAX RECOVERY
TIME
Page 38
DEFAULT
2°F (1°C)
Defines the number of degrees the temperature must go beyond a
SETPOINT prior to changing from HEAT to COOL mode or vice versa
in AUTO mode.
60 MIN
The time limit the thermostat is allowed to engage the equipment to
reach a desired temperature. The algorithm determines the time
required to reach the temperature, and engages the equipment prior to
the next Scheduled SETPOINT in order to reach the desired
temperature at the appropriate time. The temperature may not be
reached if the ANTICIPATION TIME is less than the time required to
heat (or cool) to the desired temperature.
90 MIN
The maximum time the thermostat allows the equipment to reach a
desired temperature in 1
determines that the desired temperature will not be reached, it will
engage the second (or further) stage of heating (or cooling).
ST
stage heating (or cooling). If the thermostat
OPTION
0-6°F
(0-3°C)
0 – 180 MIN
0 – 180 MIN