Heat Pump Systems
You must enter an Installer Password to access the EQUIPMENT SETTINGS from the Main Menu.
The following settings can be changed for Heat Pump Systems:
MIN ON/OFF TIME
ALLOW HP+AUX ON
BALANCE POINTS
DEFAULT
3 MIN
Minimum cycle time for the heat pump/auxiliary heater.
YES
Allows the Heat Pump and
Auxiliary Heat to be on at the
same time.
HIGH
122°F (50°C)
The High Balance Point defines the outdoor temperature above which
the Auxiliary Heater is disabled. An external temperature sensor must
be installed for the Balance Points to operate.
LOW
-40°F (-40°C)
The Low Balance Point defines the outdoor temperature below which
the Heat Pump compressor is disabled. An external temperature
sensor must be installed for the Balance Points to operate.
OPTION
1-6 MIN
NO
Does not allow Heat Pump and
Auxiliary Heat to be on at the same
time (add-on configuration).
-38 – 122°F
-39 – 50°C
-40 – 120°F
-40 – 49°C
Page 37