Installation / Alignment; Pre-Alignment Checklist - Honeywell SK-Beam Installation And Maintenance Instructions Manual

Single-ended reflected type projected beam smoke detector
Table of Contents

Advertisement

FIGURE 6. WIRING CONNECTIONS AT DETECTOR
T3
T2
FIGURE 7. WIRING DIAGRAM
T3
LISTED
+
ñ
REMOTE
POWER
SOURCE
+
* Only used for
ñ
SK-BEA M-T. See
FROM PA NEL OR
electrical ratings.
PREVIOUS DEVICE
T1
T2
T1
+ ñ
+
ñ
COMMUNICA TION LINE
TO NEX T
32 VDC MA X .
DEVICE
TWISTED PA IR IS
RECOMMENDED.
FIGURE 8. WIRING DIAGRAM (RTS451/RTS151)
PIN 1
PIN 2
PIN 4
PIN 3
PIN 5
RTS451/RTS451KEY
or RTS151/RTS151KEY
FIGURE 9. WIRING DIAGRAM (RTS451/RTS151)
SLC (+)
SLC ( –)
C0260-01
Note 1: See electrical ratings section of this

INSTALLATION / ALIGNMENT

Reference Figures 10 through 14 for installation, alignment, and maintenance.
Please make sure to complete all steps in order to ensure a successful installa-
tion. Proper application, mounting, alignment, and set-up will minimize false
alarms and nuisance trouble signals.

PRE-ALIGNMENT CHECKLIST

• Insure that both the detector and reflector are mounted securely to stable
surfaces.
• Insure that all wiring is correct.
• Insure that terminal blocks are fully seated into their receptacles on the
detector.
• Complete any wiring dressing to minimize movement to the detector once
the alignment procedure is completed.
• Insure that the appropriate number of reflectors are used for the installed
distance. Distances between 230 and 328 Feet (70 – 100 m) require ad-
ditional reflectors (4 total). The BEAMLRK accessory should be used in
these cases.
• Insure that the line of sight between the detector and reflector is clear
and that reflective objects are not too near. See Mounting Instructions
for more details.
• Insure that both the detector and reflector are mounted within their
operational parameters for off axis angles. See Mounting Instructions
ñ
+
for more details.
• Disable the zone or system to prevent unwanted alarms before applying
power.
• Insure power to the detector is "ON".
C0335-03
• Insure that the appropriate address is set on the code wheels.
You are now ready to begin the alignment procedure.
5
DETECTOR
T1-1
SLC IN +
SLC OUT +
T1-2
SLC IN –
SLC OUT –
T2-1
REMOTE ALARM OUT
T2-2
AUX (–)
T2-4
RESET INPUT
T2-3
TEST INPUT
T3-3
REMOTE TROUBLE OUTPUT
OPTIONAL YELLOW LED
BDT-SS
Alarm
Signal
T2-1
Circuit
(Note 1)
T2-2
manual for cir cuit output ratings.
T1-3
T1-4
C0328-06
Red
C0369-00
I56-3433-004
04-12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sk-beam-t

Table of Contents