Unload, Load, And Store The Power Module - Allen-Bradley PowerFlex 750 Series Installation Instructions Manual

Service cart and dc precharge module lift
Hide thumbs Also See for PowerFlex 750 Series:
Table of Contents

Advertisement

Remove the DCPC Module Lift
This section applies only to systems that contain a DC precharge module.
Follow these steps to remove the DCPC module lift.
1. Remove the DCPC module lift from the power module and service
cart.
a. Remove the rear lock plug and pin.
b. To release the front lock plug, slide the DCPC module lift toward
the service cart handle.
2. Remove the DCPC module lift from the power module and service
cart.
a. Be careful not to damage the busbar connections on the power
module, remove the DCPC module lift and place DCPC module
lift on the floor.
ATTENTION: Do not come in contact with the busbar. Damage to
the busbars can impact product integrity, leading to potential
product failure.
b. Reinsert the rear lock plug and pin.
c. Insert all tethered keys and pins for storage.
Properly store the DCPC module lift. See
DCPC Module Lift on page 29

Unload, Load, and Store the Power Module

This section applies to the LCL filter and power module but assumes that the DC precharge module and DCPC module lift are already removed
from the service cart for service or removed for temporary storage. For information on how to remove the DC precharge module from the DCPC
module lift see
Unload or Load the DC Precharge Module from the DCPC Module Lift on page
ATTENTION: It is required to remove the DCPC module lift from the power module before removing the power module from the service cart. To remove the
DCPC module lift, see
Choose a suitable storage location for the module:
• Surrounding atmosphere must not contain volatile or corrosive gas, vapors, or dust.
• Surrounding atmosphere must not contain conductive pollution.
• Surrounding air temperature: -40...+70 °C (-40...+158 °F).
• Relative humidity: 5...95% noncondensing.
• Do not store modules in active aisles and work areas.
• Store modules on a smooth and level surface clear of debris and obstacles; avoid sloped and
rough surfaces.
• Recommended to use the storage hardware (Cat. No. 20-750-MINV-ATIP).
IMPORTANT
The PowerFlex 755TM Power Module and LCL Module storage hardware (Cat. No. 20-750-MINV-
ATIP) that is shown is recommended during storage. For more information, see PowerFlex 755TM
and LCL Module Storage Hardware Installation Instructions, publication 750-IN106.
ATTENTION: Avoid equipment damage and personal injury. Use the recommended storage hardware (Cat. No. 20-750-MINV-ATIP) to minimize tip-over
hazards.
Store the Service Cart and the
for more information.
Remove the DCPC Module Lift on page
Rockwell Automation Publication 750-IN105D-EN-P - June 2018
PowerFlex 750-Series Service Cart and DC Precharge Module Lift
1a
2a
18.
19.
1b
2b
Storage Hardware (Optional)
Cat. No. 20-750-MINV-ATIP
Storage hardware is not included with service cart.