Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan(drive) o No.
Fan
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor
: D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
kW
A
A
kW
Internal thermostat, Anti-phase protector, thermal relay, HP switch, Discharge thermo, LP switch
W
kW
K/min(CFM)
dB
Cooling
mm(in.)
W
D
mm(in.)
mm(in.)
H
kg(lbs)
kg(lbs)
L
mm(in.)
Liquid
mm(in.)
Gas
Indoor side
Outdoor side
Height difference
Piping length
Indoor
D.B. 35˚C , W.B.22.5˚C
D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
PU-P5YGA
Cooling
3-ph, 50Hz, 380-415V(4wires)
5.25
8.39
79
Linear Expansion Valve
HE86YAA
4.3
Propeller (direct) o 2
95(3,360)
53
Outdoor
D.B. -5˚C
11
PU-P6YGA
Cooling
6.36
10.17
84
Munsell 5Y 8/1
Hermetic
HE101YAA
5.1
Line start
38
Plate fin coil
0.075+0.075
100(3,530)
—
55
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
122(269)
R407C
5.8(12.8)
2.0(Ester)MEL32
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m