Applications; Parallel Connection To Increase Power Rating - Siemens SITOP PSU100L 6EP1332-1LB00 Manual

Table of Contents

Advertisement

Applications

9.1

Parallel connection to increase power rating

To increase the power rating, SITOP PSU100L power supplies of the same type can be
directly connected in parallel.
The following must be observed:
● The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external connection point (terminal strip) if possible.
● The power supplies connected in parallel must be switched on simultaneously with a
common switch in the line feeder cable (e.g. with the main switch available in control
cabinets).
● The output voltages measured in no-load operation for the power supplies that are not yet
connected in parallel should not deviate more than a maximum of 50 mV. This usually
corresponds to the factory setting. If the output voltage is changed, you should connect
the "-" terminals and then, in no-load operation, measure the voltage difference between
the "+" terminals that have not yet been connected. The voltage difference should not
exceed 50 mV.
Figure 9-1
SITOP PSU100L
Manual, 08.2016, C98130-A7603-A1-2-7629
Parallel connection, correct and incorrect
9
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents