9
Check that the RUN LED indicator
on the Inverter is unlit and the
7-segment display (Output
frequency) is "0.00".
10
Enter "1" in the Operation command
to Inverter: E001_Command.
*Command bit 0: Forward/stop
0:Stop
1:Forward command
11
Check that Status:E001_Status is
"1201" and Output frequency
monitor:E001_Output_frequency_m
onitor is "100".
*Status bit 0: Forward Operation in
progress
0:Stopped/during reverse
operation
1:During forward operation
*Status bit 12: Frequency matching
0:During
acceleration/deceleration
1:Frequency matching
Command
Bit
Name
0:Stop
0
Forward/stop
1:Forward command
0:Stop
1
Reverse/stop
1:Reverse command
7
Fault reset
Resets an error or trip for the unit or Inverter.
-
(Reserved)
The reserved area. Set 0.
Status
Bit
Name
Forward
0:Stopped/during reverse operation
0
operation in
1:During forward operation
progress
Reverse
0:Stopped/during forward operation
1
operation in
1:During reverse operation
progress
0:No error or trip occurred for the unit or
3
Fault
Inverter
1:Error or trip occurred for the unit or Inverter
0:No warning occurred for the unit or Inverter
7
Warning
1:Warning occurred for the unit or Inverter
0:Local (Operations from EtherCAT are
disabled)
9
Remote
1:Remote (Operations from EtherCAT are
enabled)
Frequency
0:During acceleration/deceleration
12
matching
1:Frequency matching
Connection
0:Normal
error between
1:Error (Cannot update data for the Inverter. To
15
the Optional
restore, turn the power OFF and then ON
Unit and
again.)
Inverter
-
(Reserved)
The reserved area.
7. Connection Procedure
Meaning
Meaning
28