1.3. Sensor Units
Selects the units for the Quick Start variables (high and
low calibration point, and level, distance, or space).
1.4. Operation
sensor reference point
NO
SERVICE
LEVEL
Operation
SPACE
types
DISTANCE
Default: Distance
1.5. Low Calibration Point
Distance from Sensor Reference to Low Calibration Point: usually process empty level. See
Operation (1.4.) for an illustration.
Range: 0.0000 to 30.000 m
Values
1.6. High Calibration Point
Distance from Sensor Reference to High Calibration Point: usually process full level. See
Operation (1.4.) for an illustration.
Range: 0.0000 to 30.000 m
Values
Page EN-16
SITRANS LR260 (HART) – QUICK START MANUAL
high cal.
low cal.point
The SITRANS LR260 stops updating measurements and associ-
ated loop current. Last valid measurement is displayed.
Distance to material surface referenced from Low Calibration
Point (process empty level).
Distance to material surface referenced from High Calibration
Point (process full level).
Distance to material surface referenced from Sensor Reference
Point.
M, CM, MM, FT, IN
Options
Default: M
point
distance
space
level
A5E32106122