Technical data
6.1 Input
Input
U
Rated voltage
e rated / for
AC
Voltage range / for AC
Rated voltage Ue rated / for
DC
Voltage range / for DC
Wide-range input
Overvoltage strength
Power failure buffering
at Ia rated, min.
Power failure buffering
Rated line frequency
Line frequency range
Input current / at rated value
of input voltage 100 V/rated
value
Input current / at rated value
of input voltage 230 V
Inrush current limiting
(+ 25 °C), max.
I²t, max.
Integrated input fuse
Protection in the line feeder
cable (IEC 898)
Figure 6-1
28
6EP1332-5BA00
(24 V/2.5 A)
1-phase AC or DC
100...230 V
85...264 V
120...230 V
110...300 V
Yes
2.3 x Ue rated, 1.3 ms
20 ms
at Ue = 230 V
50/60 Hz
47...63 Hz
1.21 A
0.67 A
31 A
2.4 A²·s
Internal
Recommended miniature circuit-breaker: Characteristic B from 16 A and higher or
characteristic C from 10 A
Power failure buffering
6EP1332-5BA20
(24 V/3.7 A)
1.88 A
0.95 A
30 A
3 A²·s
Operating Instructions, 06.2013, C98130-A7599-A1-2-7629
6EP1332-5BA10
(24 V/4 A)
2.25 A
1.15 A
34 A
3 A²·s
SITOP PSU100C