Mitsubishi Electric PKFY Series Technical & Service Manual page 16

Wall mounted r410a/r407c/r22
Hide thumbs Also See for PKFY Series:
Table of Contents

Advertisement

7-2. FUNCTION OF DIPSWITCH
PKFY-P32VGM-E
Switch Pole
Function
Thermistor<Intake temperature
1
detection>position
2
Filter clogging detection
3
Filter cleaning sign
4
Air intake
SW1
5
Remote indication switching Thermostat ON signal indication Fan output indication
Mode
6
Humidifier control
Selection
7
Air flow set in case of
8
Heat thermostat OFF
9
Auto restart
10
Power source ON/OFF
SW2
Capacity
Capacity
1~6
code
P32
setting
1
Heat pump/Cooling only
2
Louver
3
Vane
4
Vane swing function
SW3
5
Vane horizontal angle
Function
6
Vane cooling limit angle setting *4 Horizontal angle
Selection
Indoor linear expansion
7
valve opening
8
Heater 4deg up
9
Target Superheat setting *5 9 degrees
10
Target Sub cool setting
SW4
Unit
1~5
Selection
OC310B
PKFY-P40VGM-E
ON
Built-in remote controller
Provided
2500hr
Effective
Always operated while the heating mode *1 Operated depends on the condition *2
Fix to LOW
Depends on setting Remote controller *3 Depends on SW1-7
Effective
Effective
SW2
Capacity
ON
ON
P40
OFF
OFF
1 2 3 4 5 6
Cooling only models
Available
Available
Available
Second setting
Effective
Not effective
15 degrees
ON
OFF
1 2 3 4 5
PKFY-P50VGM-E
Operation by switch
OFF
Indoor unit
Not provided
100hr
Not effective
*3 Fix to EXTRA LOW
Not effective
Not effective
SW2
Capacity
SW2
ON
P50
OFF
1 2 3 4 5 6
Heat pump models
Not available
Not available
Not available
First setting
Down B,C
Not effective
Effective
6 degrees
10 degrees
16
Remarks
Address board
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 10
NOTE:
*1 At Heating mode, fan
operating.
*2 At Heating mode, operat-
ing heat thermostat ON.
*3 SW1-7=OFF, SW1-8=ON
→Setting air flow.
*3
SW1-7=ON, SW1-8=ON
→Indoor fan stop.
Indoor controller board
Set while the unit is off.
<Initial setting>
Set for each capacity.
1 2 3 4 5 6
Indoor controller board
Set while the unit is off.
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 10
NOTE:
*4 At cooling mode, each
angle can be used only 1
hour.
*5 SW3-9 setting
P32 = OFF
P40 = ON
P50 = OFF
Indoor controller board
Set while the unit is off.
<Initial setting>
ON
OFF
1 2 3 4 5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pkfy-p40vgm-ePkfy-p50vgm-ePkfy-p32vgm-e