7
TROUBLE SHOOTING
7-1. HOW TO CHECK THE PARTS
PKFY-P32VGM-E
Parts name
Room temperature
Disconnect the connector then measure the resistance with a tester.
thermistor (TH21)
(Surrounding temperature 10°C~30°C)
Liquid pipe temperature
thermistor (TH22)
Gas pipe temperature
thermistor (TH23)
Vane motor
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20°C~30°C)
Orange
4
Red
5
M
2
Pink
6
1
3
Yellow
Brown
Blue
Fan motor
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20°C)
Fan
Motor terminal or
3
Red
1
White
2
2
1
Black
3
Protector
Linear expansion
Disconnect the connector then measure the resistance with a tester.
valve
(Surrounding temperature 20°C)
Blue
4
Brown
6
M
Yellow
2
5
3
1
White
Red
Orange
OC310B
PKFY-P40VGM-E
Normal
4.3k ~9.6k
Open or short
Connector
Brown - Yellow
Brown - Blue
Red - Orange
Red - Pink
relay connector
Red - Black
White - Black
Normal
(1)-(5)
(2)-(6)
White-Red
Yellow-Brown
150
PKFY-P50VGM-E
Check method
Abnormal
Normal
186 ~ 214
Normal
141.2
131.5
(3)-(5)
(4)-(6)
Orange-Red
Blue-Brown
±10%
13
Refer to the next page for the details.
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short
Refer to the next
page for the details.

Hide quick links: