Carrier 50PG20 Installation Instructions Manual page 21

Single package rooftop units electric cooling with electric heat option and comfortlink with puron (r -410a) refrigerant
Table of Contents

Advertisement

Table 5 — Electrical Data (Units With Optional Convenience Outlet) (cont)
COMPRESSOR
VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
No. 1
SIZE
(3 Ph,
50PG
60 Hz)
Min
Max RLA LRA RLA LRA RLA LRA
24
575
518
633 12.8
88
VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
No. 1
SIZE
(3 Ph,
50PG
60 Hz)
Min
Max
RLA LRA RLA LRA RLA LRA Qty
24
208/240
187 253
NA
NA
COMPRESSOR
VOLTAGE
NOMINAL
UNIT
RANGE
VOLTAGE
No. 1
SIZE
(3 Ph,
50PG
60 Hz)
Min
Max RLA LRA RLA LRA RLA LRA Qty
24
208/240
187
253 32.1 240 32.1 240
LEGEND
FLA
--- Full Load Amps
HACR --- Heating, Air Conditioning and Refrigeration
IFM
--- Indoor (Evaporator) Fan Motor
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC
--- National Electrical Code
OFM
--- Outdoor (Condenser) Fan Motor
RLA
--- Rated Load Amps
*
Fuse or HACR circuit breaker.
{ 208/230 v 75 ---kW Electric Heat units must use dual---point wiring. The main table lists the
branch circuit values for the refrigeration part of the system. The following two tables list the
branch circuit values for the electric heat and values for a feeder circuit for both branch
circuits.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
OFM
No. 2
No. 3
FLA
Qty
Hp
(ea)
12.8
88
6
0.25
0.7
Electric Heat Branch Circuit For 208/240-V 75-kW Electric Heat{
COMPRESSOR
OFM
No. 2
No. 3
FLA
Hp
(ea)
NA
NA
NA
NA
NA
NA
NA 56/75 156/180 NA
Feeder Circuit For 208/230-V Unit With 75-kW Electric Heat{
OFM
No. 2
No. 3
FLA
Hp
(ea)
6
0.25
1.5
56/75
max voltage deviation from average voltage
average voltage
ELECTRIC
POWER
IFM
HEAT
EXHAUST
kW
FLA
Hp
FLA
Qty Hp
5
6.1
2
1
7.5
9
2
1
10
11
2
1
5
6.1
2
1
24.8
24
7.5
9
2
1
10
11
2
1
5
6.1
2
1
48.3
46
7.5
9
2
1
10
11
2
1
5
6.1
2
1
78
75
7.5
9
2
1
10
11
2
1
ELECTRIC
POWER
IFM
HEAT
EXHAUST
FLA
kW
FLA
Hp
FLA
Qty
Hp
(ea)
NA
NA NA NA 156/180 175/200 180/180 200/200
ELECTRIC
POWER
IFM
HEAT
EXHAUST
kW
FLA
Hp
FLA
Qty Hp
3.7
10.6/ 9.6
2
1
5
16.7/15.2
2
1
156/180
7.5
24.2/22
2
1
10
30.8/28
2
1
Example: Supply voltage is 460-3-60
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
3. The 75-kW 208/240-v electric heat can be factory installed but it must be wired
separately in the field.
4. The convenience outlet full load amps (FLA) are 5, 3 and 3 for 208/230, 460, 575-v
units, respectively.
5. The FLA load amps provided in the table for electric heaters are based on 208/240,
480 and 600 v.
6. MCA calculation for 50PG units with electric heaters over 50 kW is = 1.25 x (IFM +
Power Exhaust + Convenience Outlet FLA amps) + 1.00 x (Electric Heater FLA).
21
POWER SUPPLY
POWER SUPPLY
WITH OPTIONAL
HACR BREAKER
FLA
MCA
MOCP*
MCA
MOCP
(ea)
42
50
42
50
2.4
47
50
47
50
45
50
45
50
2.4
50
60
50
60
47
50
47
50
2.4
52
60
52
60
42
50
42
50
2.4
47
50
47
50
45
50
45
50
2.4
51
60
51
60
48
50
48
50
2.4
54
60
54
60
69
70
69
70
2.4
75
80
75
80
73
80
73
80
2.4
79
80
79
80
75
80
75
80
2.4
81
90
81
90
86
100
86
100
2.4
92
100
92
100
90
100
90
100
2.4
96
100
96
100
93
100
93
100
2.4
99
100
99
100
POWER SUPPLY
POWER SUPPLY
WITH OPTIONAL
HACR BREAKER
MCA
MOCP*
MCA
MOCP
POWER SUPPLY
POWER SUPPLY
WITH OPTIONAL
HACR BREAKER
FLA
MCA
MOCP*
MCA
MOCP
(ea)
176/198
200/225
198/198
200/225
5.9
190/213
200/225
213/213
225/225
183/205
200/225
205/205
225/225
5.9
198/220
200/225
220/220
225/225
193/214
200/225
214/214
225/225
5.9
207/229
225/250
229/229
250/250
201/221
225/225
221/221
225/225
216/236
5.9
225/250
236/236
250/250
452 + 464 + 455
3
1371
=
3
=
457
7
= 100 x
457
= 1.53%
DISCONNECT
SIZE
FLA
45
50
48
54
50
56
45
50
48
54
50
56
63
69
67
72
69
75
97
102
100
106
102
108
DISCONNECT
SIZE
FLA
179/207
DISCONNECT
SIZE
FLA
197/224
211/237
204/230
218/244
213/238
227/252
221/245
234/259