Download Print this page

Display - Dantherm CDP 35T Service Manual

Hide thumbs Also See for CDP 35T:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 18

Display

CDG3-control
Illustration
LEDs
22
The CDP-series are equipped with an electronic CDG3-controller.
The electronics control all:
• Security functions
• Control functions
• On/off functions
The meaning of the single LEDs are described below.
On the side of the unit a display is clearly indicating the
different operation modes.
The illustration shows the display:
The table gives an overview of the meaning of the LEDs:
If the unit is switched off and restarted by connecting and disconnecting power, the
LEDs will light up green in turn before the operation mode is indicated on the display.
Part
+
+
+
Constantly green when power is connected to the unit
During defrosting and continuous ventilation there are no
display indications. In these two operation modes the
Lightning will be constantly in green to show that power is
on.
Constantly green when the compressor is running and the
unit is in dehumidification mode
Is not used in the CDP series
Lightning constantly green and drop flashing green:
When the drop flashes green and the lightning is constantly
green, the dehumidifier is working, but there has been a
failure on the unit indicated by the condenser sensor.
Disconnecting and connecting the power supply to the unit
switch off the green flashing drop
Lightning constantly green, drop flashes green, triangle
flashes red
The constant green lightning indicates that power is
connected to the unit. The drop and the triangle are flashing
on and off in green and red, respectively, to indicate that the
condenser sensor has sensed a failure. If the condenser
sensor registers a too high temperature on the condenser
coil, the compressor will be switched off and the unit will
remain stopped for 45 minutes, before it is automatically
switched on again.
After resetting, the triangle is switched off and the drop
continues to flash on and off. The flash is constantly green
Description

Advertisement

loading

This manual is also suitable for:

Cdp 45tCdp 65t