Power Wiring Interconnections - Briggs & Stratton Symphony II Installation & Operator's Manual

Power management system
Table of Contents

Advertisement

Available languages

Available languages

Power Wiring Interconnections

All wiring must be the proper size, properly supported
and protected by conduit. All wiring should be done
per applicable federal, state and local codes, standards
and regulations. Obey wire type and torque specifications
printed on the terminal blocks and neutral/ground connector.
WA RNING: Low voltage wire cannot be installed in
same conduit as power voltage wiring.
Failure to follow above warning could cause personal
injury, damage and/or malfunction of equipment.
Complete the following connections between the transfer
switch, the power manager and the main breaker panel. Also
see Wiring Decal, later in this manual.
1. Set generator's system switch to OFF position.
2. Set generator's main circuit breaker to OFF
(open) position.
NOTICE: Improper installation can cause damage to the
circuit boards and shorten their life. Installing circuit
boards in live circuits will damage the board and is not
covered by warranty. ALWAYS disconnect ALL sources of
power prior to servicing.
Remove all power prior to installing this equipment.
Failure to do so could cause internal damage to the board
when making electrical connections.
Turn generator to
OFF position.
Turn off utility power to the standby generator and
transfer switch.
Existing Fuse
Added Fuse
Holder
Holder
3. In main breaker panel, identify loads and their priorities
(using list developed with owner) that will be 'managed'
by the system.
4. In main breaker panel, turn selected load circuit
breakers to OFF position.
5. Connect "GND" lug to an approved ground.
NOTE: Assure grounding electrode conductor is connected
and bonded per applicable federal, state and local codes,
standards and regulations.
6. Install supplied fuse holder in automatic transfer switch
enclosure. Shown here is a typical install location. Clear
all metal shavings after install!
Add
GENERATOR
240VAC
Decal
Interior of
Automatic
Add
Transfer
Supplied
Switch
Fuse Holder
7. Attach supplied "GENERATOR 240VAC" decal in close
proximity to added fuse holder.
To Current
TEST
Transformers
button
To Air
Conditioner
Thermostats
To 50A MAX
General
Purpose
Loads
To
GROUND
7