Read this manual carefully to fully understand the operation.
And keep for maintenance.
WARNING : Never remodel or disassemble the equipment nor mount
nonstandard components.
This equipment shall only be used inside a metal enclosure (grounded)
in other establishments than domestic, or those that are connected to
the public power source system.

1. GENERAL DESCRIPTION

(1) Ambient condition
The type CV vacuum contactor is manufactured in accordance with IEC 60470(2000).
The vacuum contactor should be used in the following conditions.
-Ambient temperature : -5°C min. to +4O"C max.
-Relative hurnidity
CAUTION
(2) Mive condition
The location where the contactor is to be installed should be free from dust.
Corrosive gas and moisture.
When it is be used in a chemical plant or in outdoor panels,
take necessary precaiJtions against corrosion,
water seepage and condensation.
See page 2.
Table 1
Normal service condition
:
Less than 1 OOOm
Its average over a period of 24h
does not exceed +35-C
: 45% min. to 85% max.
: 20Hz -9.8m/s2 o r l e s s
:
Do not use in condition other than those specified
above , please consult