WIRING
FR-A 740-02160, 02600-EC
Screw size (M4)
Schrauben
L1 L2 L3
Power supply
FR-A 740-04320, 04810-EC
L1 L2
L3
Power supply
Screw size M12
(for option)
CAUTION
The power supply cables must be connected to R/L1, S/L2, T/L3. Never connect the power cable to the U, V, W, of the inverter. Doing
so will damaged the inverter. (Phase sequence needs not to be matched.)
Connect the motor to U, V, W. At this time turning on the forward rotation switch (signal) rotates the motor in the clockwise direction
when viewed on the motor shaft.
When wiring the inverter main circuit conductor of the FR-A740-0432005470 or more, tighten a nut from the right side of the conductor.
When wiring two wires, place wires on both sides of the conductor. (Refer to the drawing below.) For wiring, use bolts (nuts) provided
with the inverter.
6
Charge lamp
Jumper
Screw size M10
(M10)
M
3 ~
Motor
DC reactor
Screw size M10
Screw size M4
Charge lamp
Jumper
Screw size M12
Screw size
(M10)
M
3~
Motor
DC reactor
FR-A 740-03250, 03610-EC
L1 L2
L3
Power supply
Screw size M12
(for option)
FR-A 740-05470 bis 12120-EC
L1 L2
L3
Power supply
Screw size M4
Charge lamp
Jumper
Screw size M10
Screw size
(M10)
M
3~
Motor
DC reactor
Screw size M4
Charge lamp
Jumper
Schrauben M12
M
3~
Motor
DC reactor
Screw size M10