Parameters/address space
4.3 Address space
Address space for configuration as 1 x 16-channel DQ 16x230VAC/1A ST MSO
For the configuration as a 1 x 16-channel module (module-internal Shared Output, MSO),
channels 0 to 15 of the module are copied to multiple submodules. Channels 0 to 15 are
then available with identical values in various submodules. These submodules can be
assigned to up to four IO controllers when the module is used in a shared device:
● The IO controller to which submodule 1 is assigned has write access to outputs 0 to 15.
● The IO controllers to which submodule 2, 3, or 4 is assigned have read access to outputs
0 to 15.
The number of IO controllers depends on the interface module being used. Please observe
the information in the manual for the particular interface module.
Value status (Quality Information, QI)
The meaning of the value status depends on the submodule involved.
For the 1st submodule (=basic submodule), the value status 0 indicates that the value is
incorrect or that the IO controller of the basic submodule is in STOP state.
For the 2nd to 4th submodule (=MSO submodule), the value status 0 indicates that the value
is incorrect or one of the following errors has occurred:
● The basic submodule is not yet configured (not ready).
● The connection between the IO controller and the basic submodule has been interrupted.
● The IO controller of the basic submodule is in STOP or POWER OFF state.
18
Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0)
Manual, 09/2016, A5E34934069-AB