GE GPS2BHA Installation Instructions page 2

Manual motor starter

Advertisement

9 9
M4X10
Screw fitting
Catalog Number
Standard breaking capacity High breaking capacity
GPS2BSAK
GPS2BHAK
GPS2BSAL
GPS2BHAL
GPS2BSAM
GPS2BHAM
GPS2BSAN
GPS2BHAN
GPS2BSAP
GPS2BHAP
GPS2BHAR
GPS2BSAR
GPS2BHAS
GPS2BSAS
GPS2BHAT
GPS2BSAT
GPS2BHAU
GPS2BSAU
* Per UL 508 sec. 76.10, short circuit indication is required for category E
installation. Use catalog # GPAE11LLA.
* Suitable for motor group installation on a circuit capable of delivering not
more than shown below, when protected by 1500A maximum Fuses or Circuit
Breaker.
Catalog Number
GPS2BSAK
GPS2BHAK
GPS2BSAL
GPS2BHAL
GPS2BSAM
GPS2BHAM
GPS2BSAN
GPS2BHAN
GPS2BSAP
GPS2BHAP
GPS2BSAR
GPS2BHAR
GPS2BSAS
GPS2BHAS
GPS2BSAT
GPS2BHAT
GPS2BSAU
GPS2BHAU
* Per UL 508 sec. 76.10, short circuit indication is required for category E installation of GPS2BHA. Use catalog # GPAE11LLA.
These instructions do not purpose to cover all details or variations in equipment nor to provide for every possible contingency to be met in
connection with installation operation or maintenance. Should further information be desired or should particular problems arise which
are not covered sufficiently for the purchaser's purposes, the matter should be referred to the GE Company.
GE Power Controls
91±1
55±0.5
18
5.5
42
Adjustment Range
6.3 - 10
9 - 13
11 - 16
14 - 20
19 - 25
24 - 32
28 - 40
35 - 50
45 - 63
FLA Adjustment
RMS Symmetrical Amperes
Range
240V
6.3 - 10
100,000
100,000
9 - 13
100,000
11 - 16
100,000
14 - 20
100,000
19 - 25
100,000
24 - 32
100,000
28 - 40
100,000
35 - 50
100,000
45 - 63
©2000 General Electric Company
107.8
92.3
4.2
Characteristic curve
180
120
Operating Temperature at 20
60
40
20
10
6
4
2
1
40
Max. Value
20
10
Min. Value
6
4
Instantaneous
2
tripping
characteristic
1
1100% to 1560%
0.6
of maximum current
0.4
0.2
0.1
0.06
0.04
0.02
0.01
0.006
0.004
0.002
0.001
2 3 4 5 6 78 10
20 30 4050 70 100
Multiple of rated current
A
B
480V
600V
65,000
25,000
65,000
25,000
65,000
25,000
65,000
25,000
65,000
25,000
65,000
25,000
65,000
10,000
65,000
10,000
35,000
10,000
Service Factors (US only)
* For a motor with a servicefactor of
1.15 or greater, use
the motor nameplate full load
current to select the
appropriate current range.
* For motors with a service
factor less than 1.15, multiply
Max. total fault
the motor FLA by .9 and
clearing time
select the appropriate current range.
GPAPTP2A
Wire size
1 - 6 mm
18 - 8 AWG
No cutting
2
Cut before mounting
10 - 25 mm
6 - 4 AWG
2
( part A and B )
20
( 2.5 mm
13
( 1.5 mm
20
( 1.5 mm
13
( 1.0 mm
20
( 14 AWG )
AWG
13
( 16 AWG )
GE Industrial Systems
Click
part A
part B
Terminal cover
)
2
)
2
)
2
)
2
41 Woodford Ave.
Plainville, CT 06062