Cooling control:

Adaptive Defrost Control
The defrost cycle shall be started after the Defrost timer has expired. According to the following defrost procedure:
Defrost must be executed every time one of the following event occurs:
1. After 8 hours (+/-10 minutes) of compressor running, calculated considering just the thermostat function.
2. When the product goes into defrost (in thermostatic mode) a time period of 20 min (+/-1 minute) is allowed
to complete the time to defrost.
3. If the door open time > 10 min, within first 5 hrs of cumulative compressor run time, defrost is initiated at
5hrs.
4. If the door open time < 10 min or If there is at least one door opening up to 8 hrs of compressor running then
defrost time is as per point 1.
5. If there is no door opening up to 8 hrs of compressor running than defrost time will be 18hrs
6. If there is no door opening for 8 hrs, & there is door opening between 8 to 18 hrs of compressor running,
defrost will take place immediately.
th
th
The 5
, 8th or 18
independently of the number of compressor cycles and how many time the compressor was ON.
To control the temperature of your refrigerator, turn the knob
according to your requirement. This control is provided inside the
refrigerator section. Turn knob to the left to reduce the cooling and to
the right to increase the cooling. It is preset to the middle position.
hr of compressor running (defrost timer) consist of the sum of all the compressor's ON time,
8