Safety considerations
WARNING Disconnect electrical power to the i-Vu® Link before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.
i-Vu® Link
Installation Guide
Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal.
The power and network connections are also protected against transient excess
voltage/surge events lasting no more than 10 msec.
CAUTION To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
LED status indicators for EIA-485 CCN communication, Ethernet port
communication, and low battery status. Seven segment status display for
running, error, and power status.
-20 to 140°F (-29 to 60°C), 10–90% relative humidity, non-condensing
NOTE i-Vu® Link must be mounted within the building envelope.
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Rugged aluminum cover, removable screw-type terminal blocks
A:
7-1/2 in. (19.1 cm)
B:
11-5/16 in. (28.7 cm)
C:
5 in. (12.7 cm)
D:
10-7/8 in. (27.6 cm)
E:
1-1/4 in. (3.2 cm)
F:
1/4 in. (.6 cm)
Mount with 6-32 by 1/2 in. mounting screws
2-3/4 in. (7cm)
1.4 lbs (0.64 kg)
UL916 (Canadian Std C22.2 No. 205-M1983, CE, FCC Part 15 - Subpart B -
Class A
3
Introduction
CARRIER CORPORATION ©2019