Troubleshooting; Formatting The I-Vu® Link; Led's - Carrier I-Vu Link Installation Manual

Table of Contents

Advertisement

Troubleshooting

Troubleshooting
If you have problems mounting, wiring, or addressing the i-Vu® Link, contact Carrier Control Systems Support.
NOTE To help you troubleshoot, obtain a Module Status (Modstat) from the controller and review the System Error
and Warning details.
Formatting the i-Vu® Link
CAUTION This erases all archived information and user-configuration settings. You will have to reconfigure
all custom settings. It is recommended to restore the factory defaults only under the guidance of Carrier Control
Systems Support.
To erase volatile memory data and restore factory default configuration settings:
1
Turn off the i-Vu® Link's power.
2
Hold down the i-Vu® Link's Format button while you turn its power on.
3
Continue to hold down the Format button until the module status LED displays 8 and then 0, then release the
button.
4
Sets the Bus and Element number to 0, 1, which must be reverted using the Network Service Tool.
5
In the i-Vu CCN Plus/Pro interface, select the i-Vu® Link in the navigation tree, go to the Downloads page and
Download All Content to download the control programs, drivers, and parameters.

LED's

The LED's indicate if the i-Vu® Link is speaking to other devices on the network. The LED's should reflect
communication traffic based on the baud rate set. The higher the baud rate, the more solid the LED's will look.
The Module Status LED can display the following error codes.
Error
Code...
Indicates...
0
The controller is not
downloaded.
1
A custom equipment
error
i-Vu® Link
Installation Guide
Possible solutions
1
In the i-Vu CCN Plus/Prointerface, select the router in the navigation
tree, go to the Downloads page and click Download All Content.
Obtain a Module Status Report (Modstat) and look for error conditions.*
If you cannot determine the error from the Modstat, send a screenshot of
the Modstat to Technical Support.
*NOTE To obtain a Module Status Report in i-Vu CCN Plus/Pro, click the
menu button, then select Manual Command and type in "modstat".