Specifications - Carrier I-Vu Link Installation Manual

Table of Contents

Advertisement

Introduction

Specifications

Module drivers
Maximum number of CCN
controllers
Maximum number of third
party points
Power
Communication ports
Microprocessor
Memory
Battery
Real-time clock
i-Vu® Link
Installation Guide
drv_ivulink_modbus
drv_ivulink_lon
140
500
24 Vac ±10%, 50–60 Hz, 24 VA
26 Vdc ±10%, 10 W
10/100 BaseT Ethernet Port E1: LAN, BACnet IP, and/or Modbus TCP/IP
communications
Port S1: 5-pin EIA-485 for CCN Network and/or CCN Service Tool connection
(9600 and 38400 baud)
Port S2: Configurable EIA-485/EIA-232 for third party network connections,
including:
BACnet MS/TP @ 9600, 19200, 38400, and 76800 baud
Modbus (RTU and ASCII modes) @ 9600, 19200, 38400, and 76800 baud
LonWorks (requires SLTA-10 adapter) @ 38400 and 76800 baud
32-bit Motorola Power PC microprocessor with cache memory, Fast Ethernet
controller, high performance 32-bit communication co-processor
16 MB non-volatile battery-backed RAM (with 12 MB available for use), 8 MB
Flash memory, 32-bit memory bus
NOTE Shelf life of battery is 10 years with 720 hours of continuous operation.
10-year Lithium CR123A battery ensures the following data is retained for a
maximum of 720 hours during power outages:
Time
Graphics
Control programs
Editable properties
Schedules
Trends
To conserve battery life, you can set the driver to turn off battery backup after a
specified number of days and depend on the archive function to restore data
when the power returns.
A low battery is indicated by the Battery Low LED or a low battery alarm in the i-
Vu CCN Plus/Pro application, a touchscreen device, and Field Assistant.
Battery-backed real-time clock keeps track of time in event of power failure
2
CARRIER CORPORATION ©2019