Ruskin GRILLE DUCT TERMINATION Installation Instructions

Transfer openings and grille duct terminations

Advertisement

3900 Dr. Greaves Rd.
TRANSFER OPENINGS AND GRILLE DUCT TERMINATIONS
FIGURE 1
TRANSFER OPENING
CURTAIN TYPE FIRE DAMPER

APPLICATIONS

Ruskin fire and combination fire and smoke dampers with 1
termination applications. Grille installation in these applications is
3 hour fire ratings may be installed in transfer opening and grille duct
optional.
Select the damper with sleeve of sufficient length to fit flush with
wall or floor where appropriate and to permit attachment of perime-
ter mounting angles and ductwork where required. Ruskin fire and
combination fire and smoke dampers require mounting angles on
only one side of the wall or floor. Refer to the appropriate installa-
tion instructions for specific information.

GENERAL INSTALLATION

1. Install dampers within opening as defined in the appropriate
damper installation instructions sheet. Sleeve shall be flush with
wall or floor on one side of the damper for duct termination
applications and on both sides for transfer opening applications.
2. Place mounting angles around damper as shown in the appro-
priate detail above on in accordance with the specific damper
installation instruction. Mounting angles shall overlap wall or
floor a minimum of 1" (25). Mounting angles installed on flush
side of walls shall be notched in order to meet 1" (25) wall over-
3. Fasten angles to damper with type and quantity of fasten-
lap requirement at damper corners.
ers as specified and detailed in the appropriate installation
instructions for the damper model. The inverted mounting
angle on the grille side (refer to application figures above)
can be eliminated or the angle on the wall side opposite the
grille can be eliminated (refer to note #4). When a single
angle is used, the agle must be fastened to the damper
sleeve and wall or top of the floor in accordance with the
installation instructions for the damper.
Dimensions shown in parentheses ( ) indicate millimeters.
II-TRANS-514/Replaces II-TRANS-1207
Kansas City, MO 64030
INSTALLATION INSTRUCTIONS SUPPLEMENT
FIGURE 2
GRILLE DUCT TERMINATION
CURTAIN TYPE FIRE DAMPER
1
/
2
ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION.
(816) 761-7476
COMBINATION FIRE AND SMOKE DAMPER
ITEM
1.
and
2.
3.
4.
5.
6.
7.
8.
9.

NOTES:

1. For installation information not covered in this sheet, refer-
ence appropriate damper basic installation instructions.
2. Grilles are optional and supplied by others.
3. Vertical installation is shown; horizontal installation is similar.
4. 1
/
hour fire rated dampers that are 90"w x 48"h (2286 x
1
2
1219) or 48"w x 90"h (1219 x 2286) and smaller may be
installed with angles on only one side of the barrier (either
side of the wall or top of the floor).
FAX (816) 765-8955
FIGURE 3
GRILLE DUCT TERMINATION
MULTIPLE BLADE FIRE DAMPER OR
DESCRIPTION
Curtain type or multiple blade fire damper
Damper sleeve
Mounting angle (see note 4 below)
Grille (optional – supplied by others)
Duct
Duct to damper sleeve connection
Actuator (location varies)
Jackshaft (indicates damper positioning)
Access door (optional)
SEE COMPLETE MARKING
ON PRODUCT
© Ruskin 2014

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GRILLE DUCT TERMINATION and is the answer not in the manual?

Questions and answers

Summary of Contents for Ruskin GRILLE DUCT TERMINATION

  • Page 1 ITEM DESCRIPTION Curtain type or multiple blade fire damper Ruskin fire and combination fire and smoke dampers with 1 termination applications. Grille installation in these applications is 3 hour fire ratings may be installed in transfer opening and grille duct Damper sleeve optional.
  • Page 2 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 www.ruskin.com...

Table of Contents